When rooftop solar pushes the street voltage too high

Low-voltage networks were built for power to flow one way, from the substation to homes. At midday, a street full of rooftop solar sends power back the other way, and the voltage at the far end of the line can rise above the legal limit. In a case study for my review of reactive power management, I modelled a solar-rich feeder and tested which tools can keep it in range.

Sarkar, Meegahapola and Datta, IEEE Access 6, 41458 to 41489, 2018. Case study modelled in DIgSILENT PowerFactory.

Try it: keep a street within the voltage limits

Eight houses on one phase of a feeder, each 43 m apart, each with a 3 kW solar system. Australian standard AS 60038 allows 230 V plus 10% or minus 6%, so between 216.2 V and 253 V. Step through the eight scenarios from the study, or change the settings yourself.

This is a simplified model that runs in your browser, built on the feeder in the paper: 0.315 + j0.259 Ω/km lines, 43.05 m spacing, 3 kW (3.3 kVA) solar per house and 2.5% per tap step. To keep it small, it adds assumptions of its own, including the transformer impedance, the neutral return path, a 0.95 power factor for household demand, the capacitor at the middle of the street and the battery at the far end. It reproduces the pattern of results in the paper, but the published voltages come from the full PowerFactory model.

What the case study showed

ScenarioSituationResult
1Normal demand, no solarWithin limits
2Evening peak: demand rises from 2.4 kW to 12 kWToo low at the far end
3Transformer tap raisedWithin limits
4Capacitor bank added, so the tap can come back downWithin limits, with less wear on the tap changer
5All solar systems generating 3 kWToo high, from reverse power flow
6Midday: low demand, capacitors off, tap still highToo high
7Solar inverters absorb reactive powerSlightly better, but still too high
8A 50 kVA battery is addedWithin limits

The key lesson is in scenario 7. Solar inverters can help with voltage, but only within their apparent power rating: a 3.3 kVA inverter producing 3 kW of solar has little headroom left for reactive power. Holding a solar-rich street inside the limits took a combination of tools, with energy storage doing the final work.

The wider review

The case study closes a broad review of reactive power management in grids with high shares of wind and solar. The paper compares grid-code requirements, the reactive capability of different wind and solar generators, support devices such as capacitor banks and static compensators, control strategies, and optimisation algorithms. It has become my most cited work.

I later built on it with an optimal reactive power dispatch study that coupled MATLAB and PowerFactory and used particle swarm and pattern search optimisation on a modified IEEE 39-bus system with wind and solar generators (IEEE ICIT, 2019).