When rooftop solar pushes the street voltage too high
Low-voltage networks were built for power to flow one way, from the substation to homes. At midday, a street full of rooftop solar sends power back the other way, and the voltage at the far end of the line can rise above the legal limit. In a case study for my review of reactive power management, I modelled a solar-rich feeder and tested which tools can keep it in range.
Sarkar, Meegahapola and Datta, IEEE Access 6, 41458 to 41489, 2018. Case study modelled in DIgSILENT PowerFactory.Try it: keep a street within the voltage limits
Eight houses on one phase of a feeder, each 43 m apart, each with a 3 kW solar system. Australian standard AS 60038 allows 230 V plus 10% or minus 6%, so between 216.2 V and 253 V. Step through the eight scenarios from the study, or change the settings yourself.
This is a simplified model that runs in your browser, built on the feeder in the paper: 0.315 + j0.259 Ω/km lines, 43.05 m spacing, 3 kW (3.3 kVA) solar per house and 2.5% per tap step. To keep it small, it adds assumptions of its own, including the transformer impedance, the neutral return path, a 0.95 power factor for household demand, the capacitor at the middle of the street and the battery at the far end. It reproduces the pattern of results in the paper, but the published voltages come from the full PowerFactory model.
What the case study showed
| Scenario | Situation | Result |
|---|---|---|
| 1 | Normal demand, no solar | Within limits |
| 2 | Evening peak: demand rises from 2.4 kW to 12 kW | Too low at the far end |
| 3 | Transformer tap raised | Within limits |
| 4 | Capacitor bank added, so the tap can come back down | Within limits, with less wear on the tap changer |
| 5 | All solar systems generating 3 kW | Too high, from reverse power flow |
| 6 | Midday: low demand, capacitors off, tap still high | Too high |
| 7 | Solar inverters absorb reactive power | Slightly better, but still too high |
| 8 | A 50 kVA battery is added | Within limits |
The key lesson is in scenario 7. Solar inverters can help with voltage, but only within their apparent power rating: a 3.3 kVA inverter producing 3 kW of solar has little headroom left for reactive power. Holding a solar-rich street inside the limits took a combination of tools, with energy storage doing the final work.
The wider review
The case study closes a broad review of reactive power management in grids with high shares of wind and solar. The paper compares grid-code requirements, the reactive capability of different wind and solar generators, support devices such as capacitor banks and static compensators, control strategies, and optimisation algorithms. It has become my most cited work.
I later built on it with an optimal reactive power dispatch study that coupled MATLAB and PowerFactory and used particle swarm and pattern search optimisation on a modified IEEE 39-bus system with wind and solar generators (IEEE ICIT, 2019).